Large conductors cannot be bent around a tight corner without damaging their insulation, so the NEC sizes pull and junction boxes from the raceways entering them, not from volume. This free junction box sizing calculator applies the NEC 314.28 rules: enter the pull type and the raceway trade sizes, and it works out the minimum distance from the entry wall to the opposite wall, plus the minimum spacing between raceway entries.
A straight pull enters one wall and leaves through the opposite wall. An angle pull leaves through an adjacent wall, a U pull enters and leaves through the same wall, and a splice joins conductors inside the box. Angle pulls, U pulls and splices all use the same sizing rule. These rules apply to boxes containing conductors 4 AWG and larger; boxes with 6 AWG and smaller conductors are sized by box fill under NEC 314.16 instead.
Enter trade sizes in inches, not the measured outside diameter of the conduit. For an angle pull, U pull or splice, the other raceways are the ones on the same wall and row as the largest raceway. If an "other" raceway is larger than the one entered as the largest, the calculator uses the bigger one as the largest. A straight pull ignores the other raceways: only the largest size matters.
Please select a raceway size above 0.
| Largest Raceway | Straight Pull Minimum | Angle / U Pull Minimum | Distance Between Raceways |
|---|
Each row uses a different largest raceway size with the other raceways entered above. The angle and U pull minimum uses 6 times the largest raceway plus the other raceways on the same wall and row; if an "other" raceway is larger than the row size, it becomes the largest for that row.
Founder & CEO, Techraxy
Faiq Ur Rahman is a web designer, digital product developer, and Founder of Techraxy, a growing platform of online calculators and utility tools. He specializes in building structured, user-friendly tools focused on finance, health, conversions, productivity, and everyday problem-solving. He is passionate about developing practical digital solutions that make complex tasks simpler for users worldwide.
User Ratings:
ADVERTISEMENT
ADVERTISEMENT
Large conductors cannot be bent around a tight corner without damaging their insulation, so the NEC sizes pull and junction boxes from the raceways entering them, not from volume. This free junction box sizing calculator applies the NEC 314.28 rules: enter the pull type and the raceway trade sizes, and it works out the minimum distance from the entry wall to the opposite wall, plus the minimum spacing between raceway entries. A comparison table shows how the minimum size grows across raceway sizes from 1 to 4 inches, for both straight pulls and angle pulls.
A junction box sizing calculator works out the minimum dimensions of a pull or junction box that holds conductors 4 AWG and larger, using NEC 314.28(A). The rules depend on how the conductors move through the box. For a straight pull, where the conductors enter one wall and leave through the opposite wall, the distance from the raceway entry to the opposite wall must be at least eight times the trade size of the largest raceway. For an angle pull, a U pull or a splice, the distance must be at least six times the largest raceway plus the sum of the trade sizes of the remaining raceways on the same wall and row. A separate rule sets the distance between raceway entries enclosing the same conductor at six times the largest raceway, measured from the nearest edge of one opening to the nearest edge of the other, not centre to centre.
These rules exist to protect conductor insulation. A large conductor pulled around too tight a bend, or forced into a box too short for the pull, gets its insulation scraped or crushed against the raceway edge or the box wall. The 8x and 6x multipliers give the crew enough room to pull and bend the conductors without damage. The rules apply only to boxes containing conductors 4 AWG and larger; boxes with 6 AWG and smaller conductors are sized by volume under NEC 314.16 instead, which the Box Fill Calculator covers.
Straight pull, NEC 314.28(A)(1):
Minimum length = 8 x largest raceway trade size
Angle pull, U pull or splice, NEC 314.28(A)(2):
Minimum length = 6 x largest raceway trade size + sum of the trade sizes of the remaining raceways on the same wall and row
Distance between raceway entries, NEC 314.28(A)(2):
Minimum distance = 6 x largest raceway trade size, measured nearest edge to nearest edge
All sizes are raceway trade sizes in inches. The largest raceway is the biggest trade size among the raceways entered; if an “other” raceway is larger than the one entered as the largest, the bigger one governs. For a straight pull the other raceways do not enter the calculation at all.
This calculator follows NEC 2023 Article 314.28; the 8x and 6x rules are unchanged in the 2026 NEC. Confirm the edition your jurisdiction has adopted and any local amendments before you order the box.
An angle pull in a junction box, with a 2 in raceway as the largest and two other raceways of 1-1/2 in and 1 in on the same wall and row. All steps below use the unrounded values; displayed figures are rounded to two decimals only at the end.
Minimum length = 6 x 2 + 1.5 + 1 = 12 + 2.5 = 14.50 in.
Minimum length in feet = 14.50 / 12 = 1.2083333 ft, displayed as 1.21 ft.
Minimum distance between raceway entries = 6 x 2 = 12.00 in.
So the box must be at least 14.50 in (1.21 ft) from the entry wall to the opposite wall, and raceway entries enclosing the same conductor must be at least 12.00 in apart, nearest edge to nearest edge. The same raceways as a straight pull would need 8 x 2 = 16.00 in, because the straight-pull rule ignores the other raceways but uses the larger 8x multiplier.
A straight pull is when the conductors enter one wall of the box and leave through the opposite wall, travelling straight through. An angle pull is when they enter one wall and leave through an adjacent wall, turning 90 degrees inside the box. A U pull enters and leaves through the same wall, and a splice joins conductors inside the box. The straight pull needs the most length for a given raceway size (eight times the largest raceway), while angle pulls, U pulls and splices use six times the largest raceway plus the other raceways on the same wall and row.
The trade size. NEC 314.28 is written in trade sizes, which are nominal sizes in inches, not measured dimensions. A 2 in trade size conduit, for example, has an outside diameter larger than 2 inches, but the calculation uses 2. Enter the size printed on the conduit or fitting, and do not measure the outside diameter with calipers.
Size each dimension separately and use the largest result. The angle-pull rule adds only the raceways on the same wall and row as the largest raceway, so raceways on a different wall or a second row belong to a separate calculation for that wall. Work out the minimum length for each wall that has raceways entering it, and the box must satisfy the largest of those minimums in each direction. This calculator handles one wall and row at a time; repeat the calculation for each wall.
No. NEC 314.28 applies to boxes containing conductors 4 AWG and larger. Boxes with 6 AWG and smaller conductors are sized by volume under NEC 314.16, which assigns each conductor a cubic-inch allowance by gauge and compares the total with the box volume. The Box Fill Calculator covers those rules. If a box holds both sizes, the 314.28 rules govern the box dimensions because of the large conductors.
NEC 314.28(B) requires that in a pull or junction box with any dimension over 6 ft, all conductors must be cabled or racked in an approved manner, so they are supported and cannot pile up or damage each other. The sizing rules still apply, and the racking requirement is in addition to them, not instead of them.
This calculator gives estimates based on NEC 2023 Article 314.28, as reproduced in published references. It sizes one wall and row at a time; a box with raceways on several walls or rows needs a separate calculation for each wall, and the box must satisfy the largest result in each direction. The minimum length is a code minimum, not a comfortable working size: the other box dimension must still fit the raceways side by side with the minimum entry spacing, and the box must be deep enough for the conductor bend radius. The NEC edition your jurisdiction has adopted may differ, and local amendments may apply. The results are for planning and estimating only. Confirm the calculation against the adopted code text, and have the work checked by a licensed electrician and the authority having jurisdiction before ordering the box.
ADVERTISEMENT
ADVERTISEMENT