How much air does a room need, and how much air is a duct actually moving? This free cfm calculator answers both questions two ways.
Use the room method when you are sizing a fan for a room: it works out the airflow from the room volume and the air changes per hour you want. Use the velocity method when you know the air speed in a duct or vent and want the airflow it carries.
The room presets are typical design values, not code requirements: the CDC aims for 5 or more air changes per hour of clean air in occupied rooms, and the Home Ventilating Institute sizes bathroom fans at 1 CFM per square foot, about 8 air changes per hour with an 8 ft ceiling. Pick Custom to enter your own rate, and check your local building code for the rates that apply to your project.
Measure the velocity in the duct with an anemometer, or use the design velocity for the run. A common residential supply velocity is around 700 ft/min. Use the inside dimensions of the duct, and the same unit (inches) for every duct measurement.
Please enter values above 0 for the room size and the air changes per hour.
Founder & CEO, Techraxy
Faiq Ur Rahman is a web designer, digital product developer, and Founder of Techraxy, a growing platform of online calculators and utility tools. He specializes in building structured, user-friendly tools focused on finance, health, conversions, productivity, and everyday problem-solving. He is passionate about developing practical digital solutions that make complex tasks simpler for users worldwide.
User Ratings:
ADVERTISEMENT
ADVERTISEMENT
How much air does a room need, and how much air is a duct actually moving? This free cfm calculator answers both questions two ways. Enter a room’s size and the air changes per hour you want, and it gives the airflow in cubic feet per minute, cubic meters per hour and liters per second, so you can size a fan with confidence. Or enter the air velocity in a duct and the duct size, and it works out the airflow the duct carries. Room-type presets fill in typical air change rates for bedrooms, kitchens, bathrooms and more, and the Compare tab shows how the required airflow changes across air change rates or duct sizes.
CFM stands for cubic feet per minute, a volume flow rate: how many cubic feet of air pass a point every minute. It is the unit fans, blowers and ductwork are rated in, so nearly every ventilation question ends up as a CFM number. This calculator reaches that number from either end of the problem.
The room method starts from how often the air should be replaced. Air changes per hour, or ACH, counts how many times a room’s full volume of air is supplied or exhausted in one hour. A 1,152 cubic foot room at 5 air changes per hour moves 5,760 cubic feet of air per hour, which is 96 CFM. The right ACH depends on the room: moisture, cooking, people and odors all push it up, which is why a bathroom needs more air changes than a bedroom. If you already know a fan’s CFM and want the rate it gives a room, the Air Changes per Hour Calculator works the formula in reverse.
The velocity method starts from the duct. Air moving at a given speed through a known cross-section carries a fixed volume per minute: CFM equals velocity in feet per minute times area in square feet. An 8 inch round duct at 700 feet per minute carries about 244 CFM. This method is how a measured duct velocity, from an anemometer or a design table, turns into an airflow you can compare with a fan rating.
Room volume (cu ft) = length (ft) x width (ft) x ceiling height (ft)
Required airflow (CFM) = room volume (cu ft) x air changes per hour / 60
Air changes per hour = CFM x 60 / room volume (cu ft)
Airflow (CFM) = air velocity (ft/min) x duct area (sq ft)
Round duct area (sq ft) = pi x (diameter in inches / 24) squared
Rectangular duct area (sq ft) = width (in) x height (in) / 144
Airflow (m3/h) = CFM x 1.6990108
Airflow (L/s) = CFM x 0.47194745
The room presets use these typical design values for air changes per hour. They are design guidance from the sources listed below, not code requirements, and the Custom option lets you enter any rate.
Bedroom: 5 ACH. The CDC aims for 5 or more air changes per hour of clean air in occupied rooms, and published room tables give 5 to 6 for bedrooms.
Living room: 6 ACH. Published room tables give 6 to 8.
Kitchen: 7 ACH. Published room tables give 7 to 8 for residential kitchens. ASHRAE 62.2 asks for 5 ACH from a kitchen fan that runs continuously, so a continuously running fan can use the lower rate.
Bathroom: 8 ACH. The Home Ventilating Institute sizes bathroom fans at 1 CFM per square foot, which is about 8 air changes per hour with an 8 ft ceiling.
Basement: 3 ACH. Published room tables give 3 to 4.
Laundry room: 8 ACH. Published room tables give 8 to 9.
Home office: 5 ACH. Published office guidance gives 4 to 6.
The metric conversions come from NIST Special Publication 811, which lists 1 cubic foot per minute as 0.0004719474 cubic meters per second. That is 1.6990108 cubic meters per hour and 0.47194745 liters per second.
A bedroom 12 ft long, 12 ft wide, with an 8 ft ceiling, at 5 air changes per hour. All steps below use the unrounded values; displayed figures are rounded to two decimals only at the end.
Room volume = 12 x 12 x 8 = 1,152 cu ft.
Required airflow = 1,152 x 5 / 60 = 96.00 CFM.
Airflow in metric = 96 x 1.6990108 = 163.1050368 m3/h, displayed as 163.11 m3/h.
Airflow in liters per second = 96 x 0.47194745 = 45.3069552 L/s, displayed as 45.31 L/s.
So the bedroom needs a fan rated at or above 96 CFM.
Velocity example: an 8 inch round duct with air moving at 700 ft/min.
Duct area = pi x (8 / 24) squared = pi x (1 / 3) squared = 0.3490659 sq ft, displayed as 0.35 sq ft.
Airflow = 700 x 0.3490659 = 244.3460950 CFM, displayed as 244.35 CFM.
Airflow in metric = 244.3460950 x 1.6990108 = 415.1466543 m3/h, displayed as 415.15 m3/h.
Airflow in liters per second = 244.3460950 x 0.47194745 = 115.3185165 L/s, displayed as 115.32 L/s.
So the duct carries about 244.35 CFM at that velocity.
Use 5 as a starting point. The CDC’s guidance is to aim for 5 or more air changes per hour of clean air in occupied rooms, counting outdoor air, filtered air and air cleaners together, and published room tables give 5 to 6 for bedrooms. Go higher if the room has heavy occupancy, allergies or a smoke or odor source, and lower only if a designer or your local code calls for a specific rate. The calculator’s bedroom preset uses 5, and Custom lets you enter any value.
Two rules cover most bathrooms. The Home Ventilating Institute recommends 1 CFM per square foot of floor area, up to 100 square feet, so an 8 by 10 ft bathroom needs about 80 CFM. ASHRAE 62.2 and the International Residential Code set the fan itself at 50 CFM intermittent or 20 CFM continuous as a minimum. In practice, size to the larger of the two: the HVI rule usually governs in bathrooms over 50 square feet. This calculator’s bathroom preset uses 8 air changes per hour, which is the HVI rule worked out for an 8 ft ceiling.
Multiply the air velocity in feet per minute by the duct’s cross-section area in square feet. For a round duct, the area is pi times the radius squared, with the diameter in inches divided by 24 to get the radius in feet: an 8 inch duct has an area of 0.35 square feet. For a rectangular duct, multiply width by height in inches and divide by 144. At 700 feet per minute, the 8 inch round duct carries 700 times 0.349, or about 244 CFM. Measure the velocity with an anemometer at the duct, or use the design velocity for the run.
CFM is a flow rate: how much air moves per minute. ACH is an exchange rate: how many times a room’s air volume is replaced per hour. They are linked by the room volume: ACH equals CFM times 60 divided by the room volume in cubic feet. The same 100 CFM fan gives 5 air changes per hour in a 1,200 cubic foot room but only 2.5 in a 2,400 cubic foot room, which is why fan sizing starts from the room. The Air Changes per Hour Calculator on this site works the reverse direction, from a known CFM to the ACH it gives a room.
No. An oversized fan is louder, uses more energy, and can pull a house into negative pressure, drawing in unconditioned air and backdrafting combustion appliances. A bath fan far above the room’s need also wastes conditioned air. Size to the target air change rate or the code minimum, then check the fan’s rating at the static pressure your duct run creates, since a fan moves less air against resistance than its free-air rating suggests. For large exhaust fans, make-up air may be needed, and that is a job for an HVAC professional.
This calculator gives airflow estimates from the dimensions and rates you enter, using typical design values for air changes per hour. Those rates are design guidance, not code requirements: your local building code and the ASHRAE standard it adopts govern, and they may set different rates or set exhaust in CFM rather than air changes. Fan ratings fall with duct resistance, so check the rating at the static pressure of your duct run. The results are for planning and estimating only. For system design, make-up air, or any commercial or health-care work, use a licensed HVAC professional.